Jesse - as others have said it is wise to test to flange pressure test limit. An important rationale is that now you have to track ...
Hi Jesse, You would want to test the new piping at the recommended 1.5 x 285 psi. You should either remove the PSV, if possible, ...
Hello all Lets call - P d The design pressure (internal pressure) - S t The allowable stress of the ...
Hello All, Thank you for the information. This completely answers my question. Yes, it can be tested at the system design pressure, ...
1.5 x 285 psi for this carbon steel piping is the preferred general practice. It assures that the piping does not have to be retested ...