Posted By Sudhindra Hathwar 06-04-2019 09:11 AM
Found In Egroup: ASK MTI - PUBLIC DISCUSSION
\ view thread
​Hi Thanks for your valued input. Material upgradation has been considered to super duplex. Temperature here is tube inlet 35 C and outlet 45 C. Ti can not be used as shell side H is there. Chlorination and Biocide are the additional action been considered to mitigate the MIC. Thanks Regards, Sudhindra ...
Posted By Sudhindra Hathwar 06-03-2019 10:49 AM
Found In Egroup: ASK MTI - PUBLIC DISCUSSION
\ view thread
​Hello All, Greetings for the day! One of our customer are facing MIC induced pitting corrosion in sea water cooler (shell and tube heat exchanger). They want to avoid it by some biocides or through chlorination. Request to give your input on waht is the ppm of Cl allowed or safe if they want to go for ...